102.
Scanner Model Type Approx. Volts
Across Cell
Approx. Resistance*
of Cell
Ambient Temp. Limits
48PT1 Infrared 125VDC 1.5 Meg. ohms 140°F/ 60°C, -40°
48PT2 Infrared 7-15VDC 20K - 80K ohms 140°F / 60°C, -40°
69ND1 Flame Rod 280-305 VAC Infinite Tip 2460°F
1500°F/816°C, -40°
* Resistance measured with 20K Ohms/ Volt Meter
For proper Flame Signal Voltage see technical bulletin for the appropriate control.
PART NUMBER DEscriptION USE WITH
48PT1-1003
48PT1-1007
48PT1-9003
48PT1-9007
48PT1-9007W
IR Straight Head 8 feet (2440mm) leads
IR Straight Head 4 feet (1220mm) Leads
IR 90 deg. Head 8 ft. (2440mm) Leads
IR 90 deg. Head 4 ft. (1220mm) Leads
- 9007 Water Repellant
P-Series
48PT2-1003
48PT2-1007
48PT2-9003
48PT2-9007
48PT2-9007W
IR Straight Head 8 feet (2440mm) leads
IR Straight Head 4 feet (1220mm) Leads
IR 90 deg. Head 8 ft. (2440mm) Leads
IR 90 deg. Head 4 ft. (1220mm) Leads
- 9007 Water Repellant
C & D Series
P-Series
FLAME-MONITOR
MicroM
35-69 Heat Insulator for 48PT Scanners
69ND1-1000K4
69ND1-1000K6
69ND1-1000K8
Flame Rod 12 inches (305mm) 1/2 in. mount
Flame Rod 18 inch (460mm) 1/2 in. mount)
Flame Rod 24 inches (710mm) 1/2 in. mount
C, D, M-Series
MB Systems
FLAME-MONITOR
MicroM
ConTROL BULLETIN
FLAME-MonITOR E-1101
D-Series D-1020, D-30, D-4041
M-Series C-4000
MB-Systems CC-82
MicroM MC-5000
源自:深圳市湾边贸易有限公司